The clock starts when the Commission’s notice arrives.
An energy audit in Malaysia is now a legal duty for large sites, not a choice. Under the Energy Efficiency and Conservation Act 2024 (Act 861), a site that used 21,600 GJ or more of energy in 12 consecutive months must have an energy audit done by a Registered Energy Auditor.
The first audit report goes to the Energy Commission within 1 year of the Commission’s notice, then every 5 years. The report follows a fixed format with 12 parts. The audit must cover at least 80% of the site’s connected load.
This guide sets out what the law asks, what the report must hold and how to prepare. It draws on the Act, the Energy Efficiency and Conservation Regulations 2024 and the Commission’s Guidelines on Energy Audit Report (st.gov.my, read 26 Nov 2026).
What is an energy audit in Malaysia under the EECA 2024?
An EECA energy audit is a legal review that measures where a large site’s energy goes and lists the measures that would save it. Under section 9 of Act 861, a Registered Energy Auditor prepares the report in the Energy Commission’s format, and the first one is due within 1 year of the Commission’s notice.
Many pages describe an energy audit as a walk-through, a detailed audit or an investment-grade study. Those labels come from other countries and from trade bodies. The Malaysian law does not use them.
What the law sets is one audit, with one format, done by one kind of person. The Commission’s Guidelines on Energy Audit Report fix what goes in it. So the useful question for a Malaysian site is not “which type of audit do we want?” but “what must our report hold, and by when?”
The duties in one table
| Duty | What it says | Source |
|---|---|---|
| Appoint an auditor | The energy consumer must appoint a Registered Energy Auditor to conduct the audit | Act 861, section 8(2) |
| First report | Submitted to the Commission within 1 year from the date of the written notice | Regulations 2024, regulation 10(1)(a) |
| Later reports | On the fifth year, every 5 years from the last report, unless an exemption notice sets another period | Regulations 2024, regulation 10(1)(b) and (c) |
| Format | Prepared by the auditor in line with the Commission’s guidelines and submitted online | Act 861, section 9(1); Guidelines, paragraph 5.2 |
| Coverage | At least 80% of the facility’s total connected load | Guidelines, paragraph 4.1.12 |
| Baseline | At least 12 months of energy data, with production or floor-area data | Guidelines, paragraph 4.1.13 |
The Energy Commission’s energy consumer page sets out the same timeline (st.gov.my, read 26 Nov 2026).
How the audit fits with the other duties
The audit is one of four duties that start with the same notice. The site also needs a Registered Energy Manager within 3 months of the notice. It needs an energy management system within 1 year of that appointment, and a yearly report.
The audit and the manager feed each other. The audit finds the savings and sets the baseline. The manager carries the savings through the year and reports on them. The EECA 2024 guide covers all four duties together.
Which sites need an energy audit, and when is it due?
A site needs an EECA energy audit once it used 21,600 GJ or more of energy in 12 consecutive months and the Energy Commission sends its written notice. Regulation 10 of the Regulations 2024 makes the first report due within 1 year of that notice, then every 5 years.
The line is set in gigajoules, not in kWh or ringgit. That catches sites that think of their energy only as an electricity bill.
A worked example on electricity alone
One kWh is 3.6 MJ. So 1,000 kWh is 3.6 GJ, and 6,000,000 kWh is 21,600 GJ.
That means a site on electricity alone crosses the line at about 6,000,000 kWh a year. On the bill, that is about 500,000 kWh a month on average.
A factory that used 450,000 kWh a month for 12 months used 5,400,000 kWh. That is 19,440 GJ, under the line on electricity alone. If the same factory also buys natural gas, the gas counts too, in GJ. A few thousand GJ of gas could take it over.
What counts toward the 21,600 GJ
The Commission’s Guidelines on Ascertaining Energy Consumer turn every energy and energy resource the site receives into GJ, then add them up. Electricity counts. Natural gas, LPG, and steam or chilled water bought in count too, along with the other energy resources in the Act’s First Schedule.
Diesel and petrol are on neither of the Act’s lists. They are left out of the 21,600 GJ sum. The free check on the home page adds a year of kWh and your other energy in GJ against the line.
Reading the deadline
The clock starts on the day the Energy Commission’s notice arrives. Write that date down. Every deadline runs from it or from the manager’s appointment, not from the date the site first crossed the line.
The Commission’s own example: a notice on 1 January 2026 means the Registered Energy Manager is due by 31 March 2026. The first audit report, on the same notice, falls due within 1 year of that date. Our post on the day the notice arrives walks through the first week.
Who may sign an energy audit report as a registered energy auditor?
Only a Registered Energy Auditor with a valid practising certificate may sign the EECA energy audit report. Section 25(2) of Act 861 requires that certificate for any energy audit under the Act, and the Commission’s MySTEE list held 136 auditor records on 26 Nov 2026.
An REA needs two things from the Energy Commission: a certificate of registration and a practising certificate. Both are set out in the Commission’s Guide on Registration of Energy Auditor, issued 4 Aug 2026 (read 26 Nov 2026).
A practising certificate is renewed for between 1 and 3 years at a time. So an auditor registered last year may not be practising today.
How to check an auditor before you sign a quote
- Ask for the auditor’s certificate of registration number and practising certificate.
- Check both on the Commission’s list of Registered Energy Auditors on MySTEE. On 26 Nov 2026 it held 136 records, each with its certificate number, practising certificate dates and status.
- Make sure the practising certificate runs past the date the audit report will be signed.
The list names people, not firms. A firm sells the audit, but the named auditor signs it. A copy of that auditor’s certificates goes into the report.
Auditor, manager or ESCO: who does what
| Role | What they do | Where the rule sits |
|---|---|---|
| Registered Energy Auditor | Conducts the audit and signs the report | Act 861, sections 8, 9 and 25 |
| Registered Energy Manager | Runs the site’s energy management through the year and reports on it | Regulations 2024, regulation 5 |
| Energy consumer | Appoints both, verifies the audit report and submits it | Act 861, section 9; Guidelines, paragraph 5.1 |
| Energy service company | May fund and deliver savings works under contract | Commission’s ESCO list |
An REA is a different role from the Registered Energy Manager. The two often work together: the audit finds the savings, and the manager carries them through.
To become an REA, the Regulations ask for, among other routes, a degree in science, engineering, technology or architecture with at least two years of work. The person also needs experience in at least two energy audits approved by the Commission (Regulations 2024, regulation 15).
What must an energy audit report contain?
An EECA energy audit report has 12 parts in a fixed order, from cover page to appendices. The Energy Commission’s Guidelines on Energy Audit Report (GP/ST/No.49/2024, revised 1/2026) set them in paragraph 4.1, including a 12-month baseline and savings in GJ and RM for each measure.
The report is not a free-form study. Every report holds the same parts, in this order (Guidelines, paragraph 4.1, read 26 Nov 2026).
- Cover page. “Energy Audit Report for” the facility, its full address, and the REA’s name and certificate of registration number.
- Declaration. The auditor declares the audit was done and the report is accurate and follows the guidelines. The energy consumer signs an acknowledgment that it has received the report and accepts responsibility for acting on it. A copy of the REA’s certificates goes here.
- Executive summary. Objectives, scope, systems audited, the baseline in GJ, load apportioning and a table of savings measures.
- Introduction. Location, business, employees, sector, a review of the site’s energy management, and the results of any previous audit and what was done about them.
- Audit method. The steps taken, the dates of data collection and the instruments used. The instruments must be calibrated once every two years, with the calibration records in the appendix.
- How the facility runs. Processes, operating hours and the main energy-using machinery.
- Equipment and systems audited. The incoming supply, transformers and tariff, with a single-line diagram; a load profile of the main incomer over at least 7 days covering a full operating cycle; and the significant energy uses, electrical and thermal.
- Baseline. At least 12 months of energy use and cost, production or floor-area data, and a regression of energy against what drives it.
- Observations and findings. Where the energy goes, load factor, maximum demand, power factor, and findings for each system.
- Savings measures. Each measure with yearly savings in GJ and RM, cost and simple payback, grouped as no or low cost, medium cost and high cost.
- Improvement plan. Priorities, timeline and any financing or incentives the auditor recommends.
- Appendices. Data collection forms, calibration records and conversion factors.
The report is agreed and verified by the energy consumer. Then the verified copy is submitted to the Commission through its online system (paragraphs 5.1 and 5.2).
What the savings table means in practice
Each measure must show its savings in GJ as well as RM. The same 3.6 MJ per kWh rule applies. A measure that saves 100,000 kWh a year saves 360 GJ a year.
That lets the Commission compare measures across fuels. A chiller measure in kWh and a boiler measure in gas can sit in one table, on one scale.
What the baseline regression means in practice
The baseline is not just a 12-month total. The report plots energy against what drives it, such as tonnes produced in a factory or floor area in a building.
That is why the production or floor data matters as much as the bills. Without it, the auditor cannot show whether energy rose because of waste or because the plant made more.
Over the line and need an audit quote? Send your energy use and notice date through the quote form. The notice date and a year of bills are enough to start.
How much of the site must the energy audit cover?
An EECA energy audit must cover equipment and systems that together make up at least 80% of the facility’s total connected load. The Energy Commission’s Guidelines on Energy Audit Report set this in paragraph 4.1.12, and the systems that use the most energy come first.
In practice that means the auditor will not stop at the lighting. The 80% is measured on connected load, so the large plant has to be in.
A worked example of the 80% rule
Say a site has 2,000 kW of total connected load. The audited systems must add up to at least 1,600 kW.
If the chillers, air handling units and air compressors come to 1,500 kW, the auditor still needs 100 kW more. That might be the pumps or the lifts, whichever use the most energy next.
Which systems the guidelines name
The guidelines name the systems a report looks at, where the site has them.
- Electrical: lighting, chillers, cooling towers, air handling units, split units, motors, pumps, air compressors, industrial furnaces, ovens, lifts and escalators.
- Thermal: boilers, dryers, furnaces and kilns, heat exchangers, absorption chillers, co-generation, steam systems, thermal oil heaters and heat pumps.
What is measured on each system
For each one, the guidelines list what is measured.
For a chiller plant: heat balance, and sensor and flow accuracy. For air handling units: pressure drop, airflow, supply and return conditions, fresh air and room conditions.
For compressed air: output at the main header, run and idle time, pressure drop and a leak test. For a boiler: pressure, temperature, steam capacity, blowdown, flue gas analysis and efficiency.
What should you have ready before the energy audit starts?
Have at least 12 months of energy bills, matching production or floor-area data, the single-line diagram and your meter data ready on day one. The Commission’s Guidelines on Energy Audit Report need a 12-month baseline and a 7-day load profile of the main incomer, so missing data slows the audit.
The audit goes faster, and costs less, when the site hands over these on the first day.
- 12 months of energy bills or more: electricity in kWh with maximum demand, plus natural gas, LPG, steam or chilled water bought in, and any other First Schedule energy resource. The baseline needs at least 12 months.
- Production or floor data for the same months: output in tonnes or units for a factory; gross floor area, air-conditioned area, data centre area and enclosed parking area for a building.
- The single-line diagram of the electrical system, with transformer ratings and the tariff.
- The meter data you hold: main incomer and sub-meters, and any building management system trends.
- A plant list: chillers, compressors, boilers and large motors, with ratings and running hours.
- The last audit report, if there was one, and what was done about each measure.
The auditor also logs the main incomer for at least 7 days, over a full operating cycle. Agree access to the main switchroom early.
Common mistakes that cost time
- A baseline that is short. Eleven months of bills is not enough. The guidelines ask for at least 12.
- Bills without matching output data. The regression needs both, for the same months.
- An old single-line diagram. If the drawing does not match the switchroom, the auditor has to trace it.
- No sub-meters on the big plant. The auditor then has to log more systems to reach 80%, which adds days.
- Leaving the switchroom shutdown to the last minute. Loggers may need a safe window to fit.
If your building also needs an energy label, the floor-area figures overlap. The post on the building energy intensity label explains that separate rule.
What sets the price of energy audit services?
The Energy Commission sets no price for an energy audit under Act 861. Cost and time depend on site size, how much of the 80% of connected load is already metered, how many thermal systems need testing, and how complete the 12 months of data are on day one.
There is no fixed fee to compare against. So the scope in each quote matters more than the headline number.
What drives cost and time
- the size of the site, and how many buildings or production lines it has;
- how much of the 80% of connected load is already metered, and how much the auditor must log;
- how many thermal systems there are, since boiler and furnace tests take longer than electrical logging;
- how complete the bills, drawings and production data are on day one.
What to ask each firm
Ask each firm what its quote includes:
- which systems are in scope, and whether they reach 80% of connected load;
- how many days of logging, and on which incomers;
- who the named REA is, with the certificate number;
- when the draft and the final report will be ready.
Leave time for your own review and signature before the 1-year deadline. Leave time, too, for the Commission to ask for more information.
Who buys the audit
The head of engineering or the facility manager usually writes the scope. Procurement buys the audit by quotation or tender.
The person who will sign the acknowledgment page, often the plant or facility head, should see the draft before it is final. That signature accepts responsibility for acting on the report.
If a site plans to pay for the savings work out of the savings themselves, read ESCO contracts. The companies list shows firms with REAs and registered ESCOs, taken from the public registers.
What happens if the energy audit is late or rejected?
Missing the energy audit is costly. Act 861 sets a fine of up to RM50,000 for not appointing a Registered Energy Auditor (section 8(4)), and up to RM50,000 for not submitting the energy audit report or a new report the Energy Commission asks for (section 9(10)).
The two fines sit in different sections, one for the appointment and one for the report.
When the Commission sends a report back
The Commission can also send a report back. If it finds the report was not prepared under the guidelines, or its content is not enough, it can direct the site to fix it.
If the site does not fix it, the Commission can direct it to submit a new report (section 9(7) and (8)). Not submitting that new report is itself an offence under section 9(10).
This is why the 12 parts matter. A report missing its calibration records, or with a baseline under 12 months, gives the Commission a reason to return it.
Can a site skip the next audit?
After the first report, the next one is due on the fifth year. An energy consumer may apply within the first three months of the fifth year to be exempted from the next report.
It must show it has carried out significant energy efficiency measures (Act 861, section 9(3); Regulations 2024, regulation 10(2)). Keeping a record of what was done about each audited measure makes that case easier.
Where can you read the energy audit rules yourself?
You can read every energy audit rule on the Energy Commission’s own pages. The st.gov.my EECA page carries the Act, the Regulations 2024 and the Guidelines on Energy Audit Report, and the MySTEE portal lists all 136 Registered Energy Auditor records as of 26 Nov 2026.
These are the primary sources this guide was checked against on 26 Nov 2026.
- The Energy Commission’s EECA 2024 page, with the Act, the Regulations and the guidelines.
- The Commission’s registration page for energy managers and auditors, with the Guide on Registration of Energy Auditor.
- The list of Registered Energy Auditors on MySTEE, with certificate numbers and practising dates.
- The Commission’s legislation page, for the Act and its subsidiary laws.
Questions on auditor registration go to rea@st.gov.my, as the Commission’s EECA page lists (read 26 Nov 2026). For the people who want to work as a Registered Energy Manager instead, the post on energy manager training covers the course and the yearly training hours.